| Basic Technical Data |
NPTs-20/100 |
NPTs -40/100 |
NPTs -60/100 |
| Rated flow rate (m³/s (L/s)) | 0.02 (20) | 0.04 (40) | 0.06 (60) |
| Minimum head at rated conditions (m) |
100 |
100 |
100 |
| Maximum power at rated conditions (kW (hp)) |
36(49) |
65.3 (88.9) |
100(136) |
| Rated shaft speed (rpm) |
2,560 |
2,700 |
2,900 |
| Minimum pump efficiency (%) |
60 |
60 |
60 |
| Maximum cavitation allowance (m) |
3.0 |
3.0
|
3.0 |
| Maximum pump inlet pressure (kgf/cm²) |
6 |
6 |
6 |
| Maximum pump outlet pressure (kgf/cm²) |
15 |
15 |
15 |
| Maximum geometric suction lift (m) |
7.5 |
7.5 |
7.5 |
| Minimum pump flow rate at the maximum geometric suction lift and rated head (L/sec) |
10 |
20 |
30 |
| Foam concentrate proportioning range (%) |
6 |
6 |
6 |
| Dimensions (mm) |
700/900/700 |
700/900/700 |
700/900/700 |
| Total weight (kg) |
65 |
65 |
65 |